The kW calculator that gets the math right.
Convert kilowatts to amps, horsepower, kWh, BTU, kVA and more, with real formulas for single-phase, three-phase and DC circuits. Built for electricians, engineers, and serious homeowners.
What is a kilowatt (kW)?
A kilowatt (kW) is a unit of power equal to 1,000 watts. Power measures the rate at which energy is produced, transferred, or consumed. One kilowatt sustained for one hour equals one kilowatt-hour (kWh), the unit your utility bills you in.
kW is the most useful unit when you size electrical equipment because it lets you bridge between voltage, current, mechanical output (horsepower), thermal output (BTU/hr) and apparent power (kVA) using a handful of well-known formulas. Underneath all of them sits Ohm's Law (V = I × R) and its power form, Watt's Law (P = V × I): voltage, current, resistance, and power are never independent of each other.
Core kW formulas
| Conversion | Formula |
|---|---|
| kW → Amps (DC) | A = (kW × 1000) / V |
| kW → Amps (1-phase AC) | A = (kW × 1000) / (V × PF) |
| kW → Amps (3-phase AC, line-to-line) | A = (kW × 1000) / (√3 × V × PF) |
| kW → HP | HP = kW / 0.7457 |
| kW → kWh | kWh = kW × hours |
| kW → BTU/hr | BTU/hr = kW × 3412.14 |
| kW → kVA | kVA = kW / PF |
| kW → Tons (refrig.) | Tons = kW / 3.5169 |
How to use this power calculator
The calculator above updates as you type, so there's no submit button to press. Follow four steps to get a result.
- Pick a direction. Use the toggle to switch between kW → Amps and Amps → kW.
- Select your current type. Choose DC, AC single-phase, or AC three-phase (line-to-line or line-to-neutral).
- Enter the voltage. US homes run 120V or 240V; US commercial and industrial sites typically run 480V three-phase.
- Enter the power factor for AC circuits. Use 1.0 if the load is purely resistive (heaters, incandescent bulbs), or 0.8 as a working estimate if you don't know the exact value. DC has no power factor field because there's no phase shift to account for.
If you don't know your power factor, check the equipment nameplate first. Motors, transformers, and fluorescent ballasts list it directly. When no nameplate value is available, 0.8 is a safe planning estimate for a mixed commercial load, and resistive loads like water heaters and electric ranges are close enough to 1.0 that the difference rarely matters.
Active power and apparent electrical power
Every AC circuit carries two kinds of power. Active power (also called real power), measured in watts (W) or kilowatts (kW), is the power actually consumed and converted into light, heat, or motion. Apparent power, measured in volt-amps (VA) or kilovolt-amps (kVA), is the total power the source must supply to deliver that active power.
The gap between the two is reactive power, measured in kVAR, the power that inductive and capacitive loads store and release each cycle without doing useful work. The three are related by kVA² = kW² + kVAR², and the ratio between active and apparent power is the power factor: kW = kVA × PF.
This distinction matters in three practical ways. Wiring and breakers are sized for current, which tracks apparent power, so a low-PF load needs heavier conductors than its kW rating alone suggests. Generators and UPS units are rated in kVA, and their real kW output drops as PF drops. And many commercial utility contracts charge a penalty when a facility's average power factor falls below about 0.9.
| Power type | Unit | Measures | Formula |
|---|---|---|---|
| Active power | W, kW | Energy actually consumed | P = V × I × PF |
| Apparent power | VA, kVA | Total power the source supplies | S = V × I |
| Reactive power | VAR, kVAR | Power stored and released each cycle | Q = V × I × sin(φ) |
What is single-phase electric power?
Single-phase power distributes electric load through one alternating current on one hot wire, with a neutral wire completing the circuit back to the source. It's the standard for homes, small offices, and light commercial spaces, running loads like refrigerators, lights, space heaters, TVs, and hair dryers.
US single-phase service runs at 120V or 240V, 60 Hz. Frequency (Hz) is the number of times the current reverses direction and back per second; each hertz is one full cycle. That reversal is what separates AC from DC: direct current flows one way only and never changes polarity.
How to calculate single-phase power
Kilowatts from amps:
kW = PF × A × V / 1000
Power in kW equals the load's power factor (PF) multiplied by current in amps (A), multiplied by RMS voltage (V), divided by 1,000.
Amps from kilowatts:
A = 1000 × kW / (PF × V)
Current in amps equals kW multiplied by 1,000, divided by power factor multiplied by voltage. See the full single-phase kW calculator for worked examples at both 120V and 240V.
What is three-phase AC power?
Three-phase power carries three alternating currents on three conductors, each 120° out of phase with the other two. It's the standard for commercial and industrial facilities running large motors, manufacturing equipment, and central air conditioning, because it delivers more power through less copper or aluminum than three separate single-phase circuits, with steadier torque on motors and higher overall conductor efficiency.
Three-phase systems are wired in one of two configurations: delta, three wires with no neutral, or wye (star), three wires plus a neutral. US commercial buildings commonly run 480V three-phase; UK and EU installations commonly run 400V.
Three-phase power calculation formulas
kW from amps (line-to-line voltage): kW = √3 × PF × A × V / 1000
kW from amps (line-to-neutral voltage): kW = 3 × PF × A × V / 1000
Amps from kW (line-to-line voltage): A = 1000 × kW / (√3 × PF × V)
Amps from kW (line-to-neutral voltage): A = 1000 × kW / (3 × PF × V)
The only difference between the line-to-line and line-to-neutral versions is swapping √3 (about 1.732) for 3, and using the matching voltage measurement. Full worked examples live on the three-phase kW calculator.
What is the power factor?
Power factor (PF) is the ratio of real power (kW) to apparent power (kVA), always between 0 and 1. A PF of 1.0 means the load is purely resistive and every watt supplied does useful work. A PF of 0 would mean all supplied power is reactive, stored and released without producing output, a theoretical extreme you won't see in practice.
Low power factor is a cost problem, not just a technical curiosity. A motor running at PF 0.7 draws noticeably more current than one at PF 0.95 for the same real-power output, which means thicker conductors, larger breakers, and, on many commercial rate plans, a monthly penalty charge.
How to calculate power factor
Real power in watts: W = |VA| × PF = |VA| × |cos φ|
Single-phase PF: PF = 1000 × kW / (V × A)
Three-phase PF (line-to-line): PF = 1000 × kW / (√3 × V × A)
Three-phase PF (line-to-neutral): PF = 1000 × kW / (3 × V × A)
| Device or load type | Typical power factor |
|---|---|
| Resistive load (heaters, incandescent bulbs) | 1.00 |
| Electric range or water heater | 1.00 |
| LED lighting | 0.90-0.95 |
| Fluorescent lamps | 0.95 |
| Synchronous motor | 0.90 |
| Induction motor, full load | 0.85 |
| Arc furnace | 0.70-0.80 |
| Induction motor, no load | 0.35 |
Full formulas and correction methods are on the dedicated power factor calculator.
Converting kW to amps and amps to kW
Converting kW to amps
A = (1000 × kW) / (√3 × PF × V)
Take a 2 kW three-phase load at 230V with a power factor of 0.85:
- A = (1000 × 2) / (1.732 × 0.85 × 230)
- A = 2000 / 338.6
- A ≈ 5.91 A
Converting amps to kW
kW = (√3 × PF × A × V) / 1000
Reversing the same numbers, 5.91 A at 230V and PF 0.85:
- kW = (1.732 × 0.85 × 5.91 × 230) / 1000
- kW = 1999.6 / 1000
- kW ≈ 2.00 kW
If your power reading is in watts rather than kilowatts, divide by 1,000 first. If your voltage is in kilovolts, multiply by 1,000 first so both sides of the formula use consistent units.
Amperage calculator: amps to kW at 120V and 240V
These tables assume a purely resistive load (power factor 1.0) so you can read off an estimate at a glance. For motors and other inductive loads, use the calculator above with the correct power factor.
| Amps | kW at 120V |
|---|---|
| 1 A | 0.12 kW |
| 2 A | 0.24 kW |
| 3 A | 0.36 kW |
| 4 A | 0.48 kW |
| 5 A | 0.60 kW |
| 6 A | 0.72 kW |
| 7 A | 0.84 kW |
| 8 A | 0.96 kW |
| 9 A | 1.08 kW |
| 10 A | 1.20 kW |
| 12 A | 1.44 kW |
| 15 A | 1.80 kW |
| 20 A | 2.40 kW |
| 25 A | 3.00 kW |
| 30 A | 3.60 kW |
| 40 A | 4.80 kW |
| 50 A | 6.00 kW |
| 60 A | 7.20 kW |
| 80 A | 9.60 kW |
| 100 A | 12.00 kW |
| Amps | kW at 240V |
|---|---|
| 1 A | 0.24 kW |
| 2 A | 0.48 kW |
| 3 A | 0.72 kW |
| 4 A | 0.96 kW |
| 5 A | 1.20 kW |
| 6 A | 1.44 kW |
| 7 A | 1.68 kW |
| 8 A | 1.92 kW |
| 9 A | 2.16 kW |
| 10 A | 2.40 kW |
| 12 A | 2.88 kW |
| 15 A | 3.60 kW |
| 20 A | 4.80 kW |
| 25 A | 6.00 kW |
| 30 A | 7.20 kW |
| 40 A | 9.60 kW |
| 50 A | 12.00 kW |
| 60 A | 14.40 kW |
| 80 A | 19.20 kW |
| 100 A | 24.00 kW |
kVA to kW and kW to kVA
HP to kW and kW to HP
Energy calculation
Power (kW) and energy (kWh) are different quantities: power is a rate, energy is power multiplied by time. Enter an appliance's power draw, how many hours a day it runs, how many days, and your electricity rate to see the energy and cost below.
For example, a 2 kW appliance running 8 hours a day for 30 days uses 480 kWh. At the 2025 US residential average of roughly $0.16/kWh, that's about $76.80 for the month. Your actual rate can range from about $0.11/kWh in low-cost states like Idaho to $0.40/kWh or more in Hawaii, so swap in your own utility rate for an accurate figure. See the electricity bill calculator for tiered and time-of-use rate plans.
How much electric power do you need for your home or small business?
Enter your electric power current needs in amperes
- A two-bedroom home typically draws around 30 A.
- A three-bedroom home typically draws around 45 A.
- A small business typically draws 50-100 A depending on equipment.
Enter the voltage coming into your home or business
- Most US homes receive 240V split-phase service.
- Most US commercial buildings receive 480V three-phase service.
Choose single-phase or three-phase
- Houses are almost always single-phase.
- Businesses with large motors or HVAC equipment are almost always three-phase.
| Location or application | Typical current | Voltage | Estimated kW |
|---|---|---|---|
| Two-bedroom home | 30 A | 240V | 7.2 kW |
| Three-bedroom home | 45 A | 240V | 10.8 kW |
| Small business | 50-100 A | 480V (3φ) | 41-83 kW |
| Central air conditioner | 15-45 A | 240V | 3.6-10.8 kW |
| EV charger (Level 2) | 32-48 A | 240V | 7.7-11.5 kW |
| Electric water heater | 25 A | 240V | 4.5 kW |
These are service-capacity figures, the size of the wire and breaker feeding the circuit, not what actually gets consumed minute to minute. Use the home electrical load calculator to add up your specific appliances, or the generator size calculator if you're sizing backup power.
A practical guide to sizing, cost, and real-world numbers
Sizing a generator from a kW load
Generators are rated in kW (real power, what does work) and kVA (apparent power, what sets conductor and alternator size). For continuous loads, size the generator so the operating load sits between 50% and 80% of prime rating, diesels suffer wet-stacking below 30% load, and you want headroom above. To account for motor inrush, the generator must momentarily absorb 6-8 times the rated current of the largest motor at start. That's why a 30 kW continuous load in a building with a 10 HP motor may need a 50 kW generator, and it's why a circuit breaker sized only for steady-state current will nuisance-trip on motor startup.
Load demand, the actual peak draw a panel or generator has to cover at once, is almost always lower than the sum of every connected device's nameplate rating, because not everything runs simultaneously. Electricians apply demand factors from NEC Article 220 to estimate realistic peak load instead of over-sizing equipment for a peak that never happens.
kW vs HP: shaft power, electrical input, and metric quirks
Nameplate horsepower is the mechanical output at the shaft. Electrical input is higher because of losses. A NEMA Premium 10 HP motor at 92% efficiency draws about 8.11 kW input. Two HP conventions exist: mechanical (US) HP = 745.7 W, and metric (PS) HP = 735.5 W. Always check the standard when reading European nameplates.
BTU/hr, tons, and how HVAC people talk
HVAC engineers use BTU/hr for capacity and "tons" for refrigeration. One refrigeration ton equals 12,000 BTU/hr, the rate of heat needed to melt one short ton of ice in 24 hours. In kW: 1 ton = 3.517 kW. So a 5-ton residential AC is roughly 17.6 kW of cooling output, but its electrical input is much lower because the system moves heat rather than generating it; a 5-ton heat pump at COP 3.5 draws only about 5 kW of electricity.
Breakers, wire gauge, and circuit protection
Once you know the amps a load draws, a circuit breaker protects the wire feeding it by tripping before the conductor overheats. NEC 210.19 requires sizing continuous loads (running 3+ hours) at 125% of calculated current before picking a breaker: a 16 A continuous load needs a 20 A breaker at minimum. Skipping that margin is one of the most common sizing mistakes on residential and light-commercial jobs.
How much is a kilowatt-hour, really?
The US residential average in 2025 hovers near 17 cents/kWh; Hawaii pays roughly 40 cents and Idaho roughly 11 cents. In Europe, expect 25-40 cents/kWh. Multiply your daily kWh by your tariff to get the daily cost. Use the electricity bill calculator to model time-of-use plans and the EV charging cost calculator for vehicle-specific math.
Quick reference: typical loads in kW
| Load | Typical kW | Notes |
|---|---|---|
| LED bulb | 0.008-0.015 | 8-15 W |
| Fridge | 0.1-0.2 | Cycles on a duty cycle |
| Microwave | 1.0-1.5 | Short bursts |
| Electric kettle | 1.5-3.0 | 120V vs 240V |
| Window AC (8,000 BTU/hr) | 0.7-0.9 | Electrical input |
| Tesla Model 3 (Level 2 home charging) | 7.2-11.5 | 32-48 A at 240V |
| Tankless water heater | 18-27 | Needs 200 A service |
| Whole-house heat pump | 3-10 | Output far higher than draw |
| Average US home, peak | 4-8 | Demand at one moment |
| Average US home, daily energy | 30 kWh | About 1.25 kW average |
When the calculator says "N/A"
A few inputs produce no meaningful answer. Power factor must be between 0.01 and 1.00. Voltage and current must be positive. If hours = 0 in a kWh/kW conversion, the result is undefined, so the calculator shows N/A rather than guess. Negative power factors only appear in regenerative systems (a motor acting as a generator) and are out of scope for normal sizing.
Built like an instrument, not a toy
- Live, in-browser math, nothing to install, no signup
- Real engineering formulas with power-factor support
- Single-phase, three-phase (line/phase), and DC modes
- Constants sourced from IEEE/NIST reference values
- Mobile-first, fast (sub-second LCP), zero trackers
- Every page links to its formulas and reverse calculation
Every calculator on this site
Conversions
Electrical
Energy & Cost
Generators & HVAC
Frequently asked questions about kW
What is a kW calculator?+
A kW calculator converts electrical measurements, amps, volts, horsepower, BTU/hr, kVA, into kilowatts (kW), and back again. This one calculates in real time for DC, single-phase AC, and three-phase AC circuits, and shows the formula behind every result.
How do I calculate kW from amps and volts?+
Multiply volts by amps, then divide by 1,000 for DC. For single-phase AC, multiply by the power factor too: kW = (V × A × PF) / 1000. For three-phase line-to-line voltage, add a √3 multiplier: kW = (√3 × V × A × PF) / 1000.
What is the formula to convert amps to kW?+
DC: kW = (A × V) / 1000. Single-phase AC: kW = (A × V × PF) / 1000. Three-phase AC (line-to-line): kW = (√3 × A × V × PF) / 1000. Three-phase AC (line-to-neutral): kW = (3 × A × V × PF) / 1000.
How many amps is 1 kW at 120V?+
At 120V single-phase with a power factor of 1.0, 1 kW draws 8.33 A (1,000 / 120). With a typical 0.9 power factor, the same 1 kW draws about 9.26 A.
How many amps is 1 kW at 240V?+
At 240V single-phase with PF 1.0, 1 kW draws 4.17 A (1,000 / 240). That's half the current of 120V for the same power, which is why large appliances like dryers and ranges run on 240V.
How do I calculate three-phase kW?+
Use kW = (√3 × A × V × PF) / 1000 when you have line-to-line voltage (the usual case), or kW = (3 × A × V × PF) / 1000 when you have line-to-neutral voltage. √3 (about 1.732) accounts for the 120° phase spacing between the three lines.
What is the difference between kW and kVA?+
kW is real power, the power that does work. kVA is apparent power, the total power the system must supply. They're linked by power factor: kW = kVA × PF. A 100 kVA generator running at PF 0.8 delivers only 80 kW of usable output.
Is kW the same as kWh?+
No. kW measures a rate of power at one instant. kWh measures energy used over time. A 2 kW heater running for 3 hours consumes 6 kWh, the number your utility bills you for.
What is a power factor and why does it matter?+
Power factor (PF) is the ratio of real power (kW) to apparent power (kVA), ranging from 0 to 1. It matters because a low PF means a load draws more current than its kW rating suggests, which forces heavier wiring, larger transformers, and, for commercial customers, utility penalty fees.
What power factor should I use if I don't know it?+
Use 1.0 for purely resistive loads like heaters and incandescent bulbs. Use 0.8 as a reasonable estimate for a mixed load with motors or electronics. For an exact figure, check the equipment nameplate or measure it with a power meter.
How do I convert kW to amps for a three-phase system?+
Divide kW by voltage, power factor, and either √3 (line-to-line voltage) or 3 (line-to-neutral voltage), after multiplying kW by 1,000: A = (kW × 1000) / (√3 × V × PF).
How many kW does a two-bedroom house use?+
A two-bedroom home typically draws around 30 A at 240V, which works out to about 7.2 kW of service capacity. Actual daily draw is much lower since not everything runs at once; average daily energy use is closer to 20-25 kWh.
How many kW does a three-bedroom house use?+
A three-bedroom home typically draws around 45 A at 240V, about 10.8 kW of service capacity, with average daily energy use around 28-32 kWh depending on climate and appliances.
What size generator do I need for my home?+
Add up the running watts of the circuits you want to keep powered, then add the highest single starting-watt appliance on top (motors and compressors need extra current to start). Most whole-house standby generators for an average home fall between 14 kW and 22 kW; see the generator size calculator for a full worksheet.
How do I calculate kilowatt-hours from kW?+
Multiply power by time: kWh = kW × hours. A 1.5 kW appliance running for 4 hours uses 6 kWh.
What is the difference between single-phase and three-phase power?+
Single-phase power uses one alternating current and one hot wire, standard in homes and small offices. Three-phase power uses three currents 120° apart on three wires, standard in commercial and industrial buildings because it moves more power through less copper and runs large motors more smoothly.
What is line-to-line voltage versus line-to-neutral voltage?+
Line-to-line voltage is measured between any two of the three phase conductors (for example 480V or 400V). Line-to-neutral voltage is measured between one phase conductor and the neutral (for example 277V or 230V). Divide line-to-line by √3 to get line-to-neutral.
How many kW is 100 amps at 240V?+
At PF 1.0: kW = (100 × 240) / 1000 = 24 kW. At a more realistic PF of 0.9 for a mixed load: about 21.6 kW.
How do I convert horsepower to kilowatts?+
Multiply mechanical horsepower by 0.7457 to get kW: a 10 HP motor is about 7.46 kW of mechanical output. Electrical input will be higher because of motor losses, typically 10-15% more.
What is the kW formula for a DC circuit?+
kW = (V × A) / 1000. DC circuits have no power factor because there's no phase shift between voltage and current, current flows in one direction only.
How do I calculate electricity cost from kW?+
Multiply the load in kW by the hours it runs, then by your utility's price per kWh: cost = kW × hours × $/kWh. A 2 kW appliance running 8 hours a day for 30 days at $0.16/kWh costs $76.80 for the month.
What is reactive power (kVAR)?+
Reactive power is the power that inductive loads (motors, transformers, ballasts) draw and release each AC cycle without doing useful work. It's measured in kVAR and calculated as Q = kVA × sin(φ). It doesn't appear on your energy bill directly, but it drives up current draw and can trigger utility penalties.
How do I convert kVA to kW?+
Multiply kVA by the power factor: kW = kVA × PF. A 50 kVA generator at PF 0.8 supplies 40 kW of real power.
What does a power factor of 0.8 mean?+
It means 80% of the apparent power (kVA) supplied does useful work; the other 20% is reactive power moved back and forth without being consumed. A PF of 0.8 is typical for an induction motor running at full load.
Can kilowatts be converted to amps directly?+
No, not without knowing voltage. Amps and kW are linked through voltage (and, for AC, power factor): A = (kW × 1000) / V for DC, or A = (kW × 1000) / (V × PF) for single-phase AC. The same kW draws different amps at different voltages.